Luchuan County Zhiqiang Motor Factory Zhiqiang Power

Malaysia · Data Center / Critical Facilities

2 MW Data Center N+1 Standby Power in Johor, Malaysia

Three 1,200 kW Yuchai generator sets for a 2 MW critical data-center load, with N+1 redundancy, 6.3 kV windings and staged load restoration.

This page describes a project we scoped and quoted. It is a scenario and a solution, not a delivered reference - we do not publish a client name, a site photograph or a commissioning record we cannot show you.

Project overview

A proposed 2 MW critical data-center facility in Johor requires standby generation that can support the full IT and cooling load while one generator is unavailable for maintenance. The design uses three 1,200 kW sets in an N+1 arrangement: any two generators must carry the complete 2 MW load. The site runs on a 50 Hz grid, uses medium-voltage distribution and requires controlled load restoration so the UPS, chillers and pumps do not receive the entire block load at once.

What the site had to solve

Technical requirements

Required capacity

3 × 1,500 kVA / 1,200 kW installed; N+1 with any two sets carrying the 2 MW critical load

Duty rating

Standby / emergency per ISO 8528-1, including scheduled no-load and load tests

Canopy & controls

Open skid in a coordinated acoustic plant room; three-set synchronising and load-sharing control

Load type

UPS, IT cooling, chillers, pumps and building services with staged motor and block-load restoration

Environment

Tropical urban site; high ambient temperature and humidity; 50 Hz grid and project-specific compliance review

How we configured it

  1. 01Selected the TFW-1200 model around the Yuchai YC12VTD1830-D30 engine: 1,200 kW prime / 1,500 kVA per set, giving 2,400 kW with any two generators online.
  2. 02Specified TFW1200-4 alternators with 6.3 kV windings for direct connection to the medium-voltage distribution scheme, subject to final switchgear and protection coordination.
  3. 03Configured a three-set synchronising and load-sharing system with mains paralleling logic, automatic start sequencing and remote alarm reporting.
  4. 04Used staged load restoration rather than a single-step close: cooling and pump groups are reconnected in timed blocks after the generator bus is stable.
  5. 05Specified a tropical cooling package and alternator anti-condensation heaters to suit the high ambient and humidity conditions in Johor.
  6. 06Kept the sets as serviceable open-skid units inside a dedicated plant room, leaving acoustic treatment, exhaust routing and radiator airflow to the final building services design.

Product configuration

ComponentSpecification
Generator sets3 × TFW-1200, 1,200 kW / 1,500 kVA prime each, N+1 standby plant
EngineYuchai YC12VTD1830-D30, 12-cylinder 39.2 L, 50 Hz, project emission tier confirmed per order
AlternatorTFW1200-4 brushless, Class H insulation, AVR, 6.3 kV winding for this project scope
Installed capacity3,600 kW / 4,500 kVA installed; 2,400 kW available with one set out of service
Control systemThree-set synchronising and load-sharing controller with mains parallel logic and remote alarm interface
Load restorationStaged UPS, chiller, pump and building-services reconnection based on the site load profile
CoolingTropical heavy-duty radiator and alternator anti-condensation protection for the Johor environment
InstallationOpen skid in an acoustic plant room; final exhaust, airflow and protection settings by the project engineer

All specifications subject to confirmation per order. Spectrum table is the internal reference; final data per technical agreement.

What this configuration is designed to deliver

These are the effects the design targets, described as expectations rather than measured field results.

Keep reading

Power ratings follow ISO 8528-1:2018 (Prime PRP / Standby ESP), and the fuel figures are stated at ISO 3046-1:2002 standard reference conditions. Both are confirmed unit by unit on our load bank, and the test record ships with the set. Standby figures are the engine's factory standby rating from the model spectrum table — never a computed 110% of the rated output. Noise figures are typical open-type reference values, not a guaranteed sound-power level.

Get a technical quotation for your project

Send your load, country and frequency requirements — an engineer will confirm configuration, pricing and shipping.