400 kW / 500 kVA Diesel Generator
The 400 kW diesel generator set delivers 500 kVA prime power (551.25 kVA engine standby rating) on 50 or 60 Hz, powered by the Yuchai YC6T600L-D22 engine and configured for medium mines, manufacturing plants, container cranes in Vietnam, Philippines, Thailand and across Southeast Asia.
Heavy industrial workhorse: 16.35L displacement maintaining continuous G3 ISO 8528 stability.
Prime Power
400 kW
Standby Power (Engine)
441 kW
Engine
Alternator Supplier
Luchuan Zhiqiang
Frequency
50 / 60 Hz
Voltage
400/230V
Fuel @ 100%
93 L/h
Dry Weight
3470 kg
Key Specifications
| Genset Model | TFW-400 |
|---|---|
| Prime Power (Genset Rated) | 400 kW / 500 kVA |
| Standby Power (Engine Rating) | 441 kW / 551.25 kVA |
| Engine Rating (Prime / Standby) | 401 / 441 kW |
| Rated Current (400V) | 720 A |
| Frequency | 50 / 60 Hz |
| Rated Voltage | 400/230V & 380/220V |
| Engine | YC6T600L-D22 (Yuchai) |
| Cylinders | 6 · 16.35 L |
| Aspiration | Turbocharged & Intercooled (ATAAC) |
| Governor | Electronic |
| Matched Alternator Supplier | Luchuan Zhiqiang |
| Fuel Consumption (100% load) | 93 L/h |
| Fuel Rate | 195 g/kWh |
| Oil Capacity | 52 L |
| Noise (Typical, Open / Silent) | 98 dB(A) / 72 dB(A) |
| Dimensions (L×W×H) | 3600 × 1250 × 1960 |
| Dry Weight | 3470 kg |
| Cooling | Tropical 50°C Heavy Radiator with Pusher/Puller Fan Guard |
| Emission | Non-road T2 |
Power ratings follow ISO 8528-1:2018 (Prime PRP / Standby ESP), and the fuel figures are stated at ISO 3046-1:2002 standard reference conditions. Both are confirmed unit by unit on our load bank, and the test record ships with the set. Standby figures are the engine's factory standby rating from the model spectrum table — never a computed 110% of the rated output. Noise figures are typical open-type reference values, not a guaranteed sound-power level.
All specifications subject to confirmation per order. Spectrum table is the internal reference; final data per technical agreement.
Estimated Fuel Consumption
Fuel consumption varies with load, ambient temperature, fuel quality and test conditions. Figures below are estimates at 50 Hz / 400V under standard conditions; do not read them across as 60 Hz delivery data, which is confirmed per order.
| Load | 50% | 75% | 100% | 110% (1h) |
|---|---|---|---|---|
| Fuel Consumption (L/h) | 50.2 | 71.6 | 93 | 105.1 |
Applications
Frequently Asked Questions
Background reading: how load changes liters per hour and choosing 50Hz vs 60Hz for your grid.
How much fuel does a 400 kW generator use?▼
At 100% load the 400 kW set consumes about 93 L/h (71.6 L/h at 75%, 50.2 L/h at 50%). Actual consumption depends on load profile, ambient conditions and fuel quality.
Is the 400 kW set prime or standby rated?▼
The set is rated 400 kW prime / 500 kVA, and the Yuchai YC6T600L-D22 engine it ships with is rated 401 kW prime / 441 kW standby in the factory model spectrum table. Prime rating suits continuous or variable load; the standby figure is the engine's factory standby rating, not a computed 110% of rated output. Confirm the duty with your engineer before ordering.
What voltage and frequency can it run at?▼
400/230V & 380/220V, selectable 50 or 60 Hz. The alternator is calibrated per order; confirm your local grid configuration. Where a model is quoted at 60 Hz, the 60 Hz rating is confirmed on the order.
Can this generator be supplied for Vietnam?▼
This model is actively supplied to Vietnam, Philippines, Thailand, Malaysia, Myanmar, Indonesia, Singapore. Import duties and documentation depend on the destination country, HS code and applicable trade agreements (for example ACFTA Form E eligibility). Confirm requirements before shipment.
What options are available (open, silent, container)?▼
Open skid, silent canopy, containerized and trailer configurations are available on request. Options affect noise level, dimensions, weight and price.
Target Markets
🇻🇳 Diesel Generators in Vietnam
220V / 380V · 50Hz
🇵🇭 Diesel Generators in Philippines
220V / 380V / 480V · 60Hz (1800 RPM)
🇹🇭 Diesel Generators in Thailand
230V / 400V · 50Hz
🇲🇾 Diesel Generators in Malaysia
240V / 415V · 50Hz
🇲🇲 Diesel Generators in Myanmar
220V / 380V · 50Hz
🇮🇩 Diesel Generators in Indonesia
220V / 380V · 50Hz
🇸🇬 Diesel Generators in Singapore
230V / 400V · 50Hz
Other Models
Get a technical quotation for your project
Send your load, country and frequency requirements — an engineer will confirm configuration, pricing and shipping.