Luchuan County Zhiqiang Motor Factory Zhiqiang Power
← Back to all models

400 kW / 500 kVA Diesel Generator

The 400 kW diesel generator set delivers 500 kVA prime power (551.25 kVA engine standby rating) on 50 or 60 Hz, powered by the Yuchai YC6T600L-D22 engine and configured for medium mines, manufacturing plants, container cranes in Vietnam, Philippines, Thailand and across Southeast Asia.

Heavy industrial workhorse: 16.35L displacement maintaining continuous G3 ISO 8528 stability.

Prime Power

400 kW

Standby Power (Engine)

441 kW

Alternator Supplier

Luchuan Zhiqiang

Frequency

50 / 60 Hz

Voltage

400/230V

Fuel @ 100%

93 L/h

Dry Weight

3470 kg

Key Specifications

Genset ModelTFW-400
Prime Power (Genset Rated)400 kW / 500 kVA
Standby Power (Engine Rating)441 kW / 551.25 kVA
Engine Rating (Prime / Standby)401 / 441 kW
Rated Current (400V)720 A
Frequency50 / 60 Hz
Rated Voltage400/230V & 380/220V
EngineYC6T600L-D22 (Yuchai)
Cylinders6 · 16.35 L
AspirationTurbocharged & Intercooled (ATAAC)
GovernorElectronic
Matched Alternator SupplierLuchuan Zhiqiang
Fuel Consumption (100% load)93 L/h
Fuel Rate195 g/kWh
Oil Capacity52 L
Noise (Typical, Open / Silent)98 dB(A) / 72 dB(A)
Dimensions (L×W×H)3600 × 1250 × 1960
Dry Weight3470 kg
CoolingTropical 50°C Heavy Radiator with Pusher/Puller Fan Guard
EmissionNon-road T2

Power ratings follow ISO 8528-1:2018 (Prime PRP / Standby ESP), and the fuel figures are stated at ISO 3046-1:2002 standard reference conditions. Both are confirmed unit by unit on our load bank, and the test record ships with the set. Standby figures are the engine's factory standby rating from the model spectrum table — never a computed 110% of the rated output. Noise figures are typical open-type reference values, not a guaranteed sound-power level.

All specifications subject to confirmation per order. Spectrum table is the internal reference; final data per technical agreement.

Estimated Fuel Consumption

Fuel consumption varies with load, ambient temperature, fuel quality and test conditions. Figures below are estimates at 50 Hz / 400V under standard conditions; do not read them across as 60 Hz delivery data, which is confirmed per order.

Load50%75%100%110% (1h)
Fuel Consumption (L/h)50.271.693105.1

Applications

Medium MinesManufacturing PlantsContainer Cranes

Frequently Asked Questions

Background reading: how load changes liters per hour and choosing 50Hz vs 60Hz for your grid.

How much fuel does a 400 kW generator use?▼

At 100% load the 400 kW set consumes about 93 L/h (71.6 L/h at 75%, 50.2 L/h at 50%). Actual consumption depends on load profile, ambient conditions and fuel quality.

Is the 400 kW set prime or standby rated?▼

The set is rated 400 kW prime / 500 kVA, and the Yuchai YC6T600L-D22 engine it ships with is rated 401 kW prime / 441 kW standby in the factory model spectrum table. Prime rating suits continuous or variable load; the standby figure is the engine's factory standby rating, not a computed 110% of rated output. Confirm the duty with your engineer before ordering.

What voltage and frequency can it run at?▼

400/230V & 380/220V, selectable 50 or 60 Hz. The alternator is calibrated per order; confirm your local grid configuration. Where a model is quoted at 60 Hz, the 60 Hz rating is confirmed on the order.

Can this generator be supplied for Vietnam?▼

This model is actively supplied to Vietnam, Philippines, Thailand, Malaysia, Myanmar, Indonesia, Singapore. Import duties and documentation depend on the destination country, HS code and applicable trade agreements (for example ACFTA Form E eligibility). Confirm requirements before shipment.

What options are available (open, silent, container)?▼

Open skid, silent canopy, containerized and trailer configurations are available on request. Options affect noise level, dimensions, weight and price.

Target Markets

Other Models

Get a technical quotation for your project

Send your load, country and frequency requirements — an engineer will confirm configuration, pricing and shipping.