Luchuan County Zhiqiang Motor Factory Zhiqiang Power
← Back to all models

2000 kW / 2500 kVA Diesel Generator

The 2000 kW diesel generator set delivers 2500 kVA prime power (3032.5 kVA engine standby rating) on 50 or 60 Hz, powered by the Yuchai YC16VC3300-D31 engine and configured for megawatt utility generation, tier-iv cloud centers, large smelting operations in Vietnam, Philippines, Thailand and across Southeast Asia.

Megawatt Class V-16 flagship. 105.56L displacement with 4-bolt reinforced main bearing structure. Supports ISO 8528-5 G3 standards.

Prime Power

2000 kW

Standby Power (Engine)

2426 kW

Alternator Supplier

Luchuan Zhiqiang

Frequency

50 / 60 Hz

Voltage

400V / 6.3kV / 10.5kV / 13.8kV

Fuel @ 100%

476 L/h

Dry Weight

18500 kg

Key Specifications

Genset ModelTFW-2000
Prime Power (Genset Rated)2000 kW / 2500 kVA
Standby Power (Engine Rating)2426 kW / 3032.5 kVA
Engine Rating (Prime / Standby)2205 / 2426 kW
Rated Current (400V)3600 A
Frequency50 / 60 Hz
Rated Voltage400V / 6.3kV / 10.5kV / 13.8kV
EngineYC16VC3300-D31 (Yuchai)
Cylinders16 · 105.56 L
AspirationTwin-Turbocharged & Water-to-Air Aftercooled
GovernorElectronic Unit Pump (EUP)
Matched Alternator SupplierLuchuan Zhiqiang
Fuel Consumption (100% load)476 L/h
Fuel Rate195 g/kWh
Oil Capacity430 L
Noise (Typical, Open / Silent)102 dB(A) / 75 dB(A)
Dimensions (L×W×H)7300 × 2800 × 3200
Dry Weight18500 kg
CoolingTropical 50°C Heavy Radiator with Pusher/Puller Fan Guard
EmissionNon-road T3

Power ratings follow ISO 8528-1:2018 (Prime PRP / Standby ESP), and the fuel figures are stated at ISO 3046-1:2002 standard reference conditions. Both are confirmed unit by unit on our load bank, and the test record ships with the set. Standby figures are the engine's factory standby rating from the model spectrum table — never a computed 110% of the rated output. Noise figures are typical open-type reference values, not a guaranteed sound-power level.

All specifications subject to confirmation per order. Spectrum table is the internal reference; final data per technical agreement.

Estimated Fuel Consumption

Fuel consumption varies with load, ambient temperature, fuel quality and test conditions. Figures below are estimates at 50 Hz / 400V under standard conditions; do not read them across as 60 Hz delivery data, which is confirmed per order.

Load50%75%100%110% (1h)
Fuel Consumption (L/h)257366.5476537.9

Applications

Megawatt Utility GenerationTier-IV Cloud CentersLarge Smelting Operations

Frequently Asked Questions

Background reading: how load changes liters per hour and choosing 50Hz vs 60Hz for your grid.

How much fuel does a 2000 kW generator use?▼

At 100% load the 2000 kW set consumes about 476 L/h (366.5 L/h at 75%, 257 L/h at 50%). Actual consumption depends on load profile, ambient conditions and fuel quality.

Is the 2000 kW set prime or standby rated?▼

The set is rated 2000 kW prime / 2500 kVA, and the Yuchai YC16VC3300-D31 engine it ships with is rated 2205 kW prime / 2426 kW standby in the factory model spectrum table. Prime rating suits continuous or variable load; the standby figure is the engine's factory standby rating, not a computed 110% of rated output. Confirm the duty with your engineer before ordering.

What voltage and frequency can it run at?▼

400V / 6.3kV / 10.5kV / 13.8kV, selectable 50 or 60 Hz. The alternator is calibrated per order; confirm your local grid configuration. Where a model is quoted at 60 Hz, the 60 Hz rating is confirmed on the order.

Can this generator be supplied for Vietnam?▼

This model is actively supplied to Vietnam, Philippines, Thailand, Malaysia, Myanmar, Indonesia, Singapore. Import duties and documentation depend on the destination country, HS code and applicable trade agreements (for example ACFTA Form E eligibility). Confirm requirements before shipment.

What options are available (open, silent, container)?▼

Open skid, silent canopy, containerized and trailer configurations are available on request. Options affect noise level, dimensions, weight and price.

Target Markets

Other Models

Get a technical quotation for your project

Send your load, country and frequency requirements — an engineer will confirm configuration, pricing and shipping.